Weil-McLain · Boiler
BOILER OUT OPEN Boiler outlet sensor open circuit
What the control is telling you
The control reads an open circuit on the boiler outlet temperature sensor.
Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)
Likely causes
- Broken, cut or unplugged sensor wire
- Failed sensor
Test and repair steps
- Turn off power to the boiler before unplugging connectors or measuring resistance.
- Check the sensor wiring for breaks, cuts or loose connectors all the way back to the control.
- Unplug the sensor and measure its resistance. Compare to the Table 10 resistance chart (p.63) at the water temperature.
- Replace the sensor if it is outside the range.
Other codes on the same units
- L1 POLARITY Line voltage polarity reversed
- AUTO LIMIT Auto-reset limit circuit open
- BOILER OUT SHORT Boiler outlet sensor shorted
- CH VOLTAGE HIGH Too much voltage on the CH / Thermostat 1 input
- CONFIG MISMATCH Stored configuration does not match the harness
- CONFIGURATION Control board not configured
- DHW VOLTAGE HIGH Too much voltage on the DHW / Thermostat 2 input
- FALSE FLAME Flame sensed when the gas valve is off
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Table 11 Control fault information and troubleshooting, p.66. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.