Weil-McLain · Boiler
CONFIGURATION Control board not configured
What the control is telling you
The control has not been set up for this boiler yet. The display is red and the boiler will not fire until the configuration is confirmed.
Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)
Likely causes
- New or replacement control that has never been configured
- Missing 24 VAC on the model-setting pins of P13 (harness problem)
Test and repair steps
- Turn off power to the boiler before unplugging connectors or measuring resistance. Restore power only for the voltage checks.
- Check the configuration number the control shows: CGa natural gas = 15, CGa propane = 5.
- Number matches the boiler press Enter to configure the control.
- Number is wrong measure 24 VAC at P13. Natural gas needs it on pins 2, 3, 4 and 5. Propane needs it on pins 3 and 5.
- Fix the harness or connector if the voltage is missing, then confirm the configuration.
- Do not run the boiler on a wrong configuration.
Other codes on the same units
- AUTO LIMIT Auto-reset limit circuit open
- BOILER OUT OPEN Boiler outlet sensor open circuit
- BOILER OUT SHORT Boiler outlet sensor shorted
- CH VOLTAGE HIGH Too much voltage on the CH / Thermostat 1 input
- CONFIG MISMATCH Stored configuration does not match the harness
- DHW VOLTAGE HIGH Too much voltage on the DHW / Thermostat 2 input
- FALSE FLAME Flame sensed when the gas valve is off
- FLAME LOST Flame lost while running
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Table 11 Control fault information and troubleshooting, p.64. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.