Weil-McLain · Boiler

BOILER OUT SHORT Boiler outlet sensor shorted

High severity Weil-McLain CGa Series 4

What the control is telling you

The control reads a short (no resistance) on the boiler outlet temperature sensor.

Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)

Likely causes

  • Pinched or shorted sensor wire
  • Failed sensor

Test and repair steps

  1. Turn off power to the boiler before unplugging connectors or measuring resistance.
  2. Check the sensor wiring for pinched or damaged spots that could short.
  3. Measure the sensor resistance and compare to Table 10 (p.63).
  4. Replace the sensor if it is outside the range.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Table 11 Control fault information and troubleshooting, p.66. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.