Weil-McLain · Boiler

DHW VOLTAGE HIGH Too much voltage on the DHW / Thermostat 2 input

Medium severity Weil-McLain CGa Series 4

What the control is telling you

The control sees more than the normal 24 VAC on the DHW (tank) thermostat input.

Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)

Likely causes

  • Shorted or miswired harness (line voltage or another source on the input)
  • Transformer putting out too much voltage
  • High 120 VAC supply

Test and repair steps

  1. Unplug control connector P3 and measure the voltage between connector pins 4 and 6.
  2. Normal 24 VAC or less there look for a short in the harness.
  3. Over 24 VAC measure the transformer output at P1 pins 6 and 7 with P1 still plugged in.
  4. Transformer output over 24 VAC replace the transformer. Transformer output normal: check the 120 VAC supply.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Table 11 Control fault information and troubleshooting, p.67. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.