Low severity Ultra Series 4

What the control is telling you

Communication between the display and the control is lost for 30 seconds. Clears automatically when communication returns.

Applies to: Ultra Series 4 boilers

Likely causes

  • Loose connection at the molex plug on the control
  • Loose connection on the back of the display

Test and repair steps

  1. Check the molex plug on the control for a loose connection.
  2. Check the connection on the back of the display.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Ultra Series 4 boiler manual, p. 121. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.