BLOWER FAULT Blower speed fault

High severity Ultra Series 4

What the control is telling you

Blower cannot reach required speed or does not reach 0 RPM when off. Resets automatically after 1 hour or from manual reset on the screen.

Applies to: Ultra Series 4 boilers

Likely causes

  • Loose or damaged blower harness or connections
  • Blower not stopping (reads non-zero RPM in standby)
  • No 120 V at blower motor or U-Control
  • Failed blower or U-Control

Test and repair steps

  1. Check the wire harness for loose connections and pin engagement at the blower, chassis mount and U-Control; check continuity.
  2. With the boiler in standby and blower off, check DIAGNOSTICS - INPUTS. If BLOWER SPEED is not 0 RPM, replace the blower.
  3. During ignition, check for 120 V at the blower connection. If 120 V is present and the blower does not start, replace the blower.
  4. Check power at the U-Control. If 120 V is not present when the boiler is powered, replace the U-Control.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Ultra Series 4 boiler manual, p. 122. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.