Weil-McLain · Boiler
AIR PRESSURE SW FAULT Air pressure switch input open
What the control is telling you
Air pressure switch input is open. Residential Ultra boilers do not use an air pressure switch; they use a wire jumper between P7 pins 4 and 5. Reset from the manual reset screen.
Applies to: Residential Ultra Series 4 boilers
Likely causes
- Boiler size selected in the U-Control does not match the rating label
- Missing or misplaced jumper between P7 pins 4 and 5
Test and repair steps
- Compare the boiler size selected in the U-Control with the rating label; correct it if needed.
- Check the P7 connection (Figure 111, page 96 and Figure 112, page 97) and confirm the jumper is between pins 4 and 5.
- Reset from the manual reset screen.
Other codes on the same units
- BLOWER FAULT Blower speed fault
- DISPLAY COMM Display communication lost
- EXP BOARD COM FAULT Expansion board to U-Control communication fault
- FLAME FAULT Flame detected when no flame should exist
- FLUE TEMP TOO HIGH Flue gas temperature too high
- GAS PRESSURE SW FAULT Gas pressure switch open
- GAS VALVE FAULT Gas valve output circuit fault
- GV FAULT EXPANSION BRD Expansion board gas valve output fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Ultra Series 4 boiler manual, p. 123. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.