Weil-McLain · Boiler
FLAME FAULT Flame detected when no flame should exist
What the control is telling you
Flame is sensed when the burner should be off. Reset from the manual reset screen.
Applies to: Ultra Series 4 boilers
Likely causes
- Burner running too hot from incorrect combustion
- Gas valve or venturi not shutting off flame
- Flame sensed after the gas valve closes
Test and repair steps
- Force the boiler to high fire.
- Check flue gases with a combustion analyzer and correct them using the maintenance and startup procedure.
- Confirm FLAME SIGNAL drops to zero on DIAGNOSTICS - INPUTS when the gas valve closes.
- With the burner off, watch the flame through the observation port.
- If flame continues after shutdown, replace the gas valve and venturi.
Other codes on the same units
- BLOWER FAULT Blower speed fault
- DISPLAY COMM Display communication lost
- EXP BOARD COM FAULT Expansion board to U-Control communication fault
- FLUE TEMP TOO HIGH Flue gas temperature too high
- GAS PRESSURE SW FAULT Gas pressure switch open
- GAS VALVE FAULT Gas valve output circuit fault
- GV FAULT EXPANSION BRD Expansion board gas valve output fault
- HIGH TEMP LIMIT High temperature limit reached
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Ultra Series 4 boiler manual, p. 121. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.