Weil-McLain · Boiler

FAULT MANUAL LIMIT Manual limit fault

High severity EGPEGSeries 7

What the control is telling you

The display shows this fault when a manual reset limit in the external limit circuit has shut the boiler down. The control needs a manual reset after the limit condition is cleared.

Applies to: Unity-CI control with P4 external limit wiring

Likely causes

  • External manual reset limit has opened

Test and repair steps

  1. Find out why the manual reset limit opened and correct the condition.
  2. Confirm the limit circuit is closed and the boiler limit is set at least 20°F below the external limit.
  3. Clear the fault using the manual reset procedure.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: EG / PEG Series 7 boiler manual, p. 40. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.