HIGH TEMP LIMIT High temperature limit reached

High severity Ultra Series 4

What the control is telling you

Boiler temperature sensor reached the high temp limit setting (no higher than 200°F). Reset from the manual reset screen.

Applies to: Ultra Series 4 boilers

Likely causes

  • Isolation valves closed
  • Circulators not programmed correctly in the U-Control
  • Incorrect primary/secondary piping
  • Undersized near-boiler piping
  • Undersized or wrong circulator

Test and repair steps

  1. Make sure all isolation valves are open.
  2. Check that circulators are programmed correctly in the U-Control for each priority (refer to the U-Control setup section).
  3. Check piping is primary/secondary as in Figure 4, page 11.
  4. Confirm near-boiler pipe meets the minimum size for the model (see setting table).
  5. Confirm circulator size matches boiler size and system needs (see page 10 and the circulator table).
  6. Reset from the manual reset screen.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Ultra Series 4 boiler manual, p. 121. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.