Weil-McLain · Boiler

IGNITION FAULT No flame after 5 ignition attempts

High severity Ultra Series 4

What the control is telling you

Boiler made 5 ignition attempts and never detected flame. Resets automatically after 1 hour or from manual reset on the screen.

Applies to: Ultra Series 4 boilers

Likely causes

  • Condensate trap blocked, letting condensate build up in the heat exchanger
  • Fouled, worn, bent or faulty igniter
  • Dirty burner or heat exchanger causing high back pressure
  • Incorrect combustion settings
  • Incoming gas pressure out of range
  • Wrong boiler or altitude selected in the control
  • Blocked flue or intake pipe
  • Loose burner fasteners or gaskets
  • Faulty venturi gaskets or wrong propane orifice
  • Ignition cable resistance out of range

Test and repair steps

  1. Check the condensate trap for blockage and clear it.
  2. Inspect the igniter. Clean a fouled igniter with fine grit sandpaper or steel wool; replace a worn or badly fouled igniter.
  3. Set igniter rods parallel with a 3.5 mm (0.138 in) spark gap.
  4. Clean the burner and heat exchanger with the flue cleaning tool and rinse method in the maintenance section if they are dirty.
  5. Check combustion on high and low fire and adjust per setup instructions if needed.
  6. Check incoming gas pressure with the boiler off and at high fire. Keep within the limits on the rating label.
  7. Confirm the correct boiler model is selected in the control and high altitude is selected at 5,500 ft or above.
  8. Check the ignition cable resistance; it should read 1000 Ohms (±50 Ohms).
  9. Check the flue pipe and intake pipe for restrictions or blockage.
  10. Check burner fasteners, gaskets, venturi gaskets and propane orifice.

Other codes on the same units

Sequence of operation

What the unit does around this code, step by step.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Ultra Series 4 boiler manual, p. 122. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.