Weil-McLain · Boiler
IGNITION FAULT No flame after 5 ignition attempts
What the control is telling you
Boiler made 5 ignition attempts and never detected flame. Resets automatically after 1 hour or from manual reset on the screen.
Applies to: Ultra Series 4 boilers
Likely causes
- Condensate trap blocked, letting condensate build up in the heat exchanger
- Fouled, worn, bent or faulty igniter
- Dirty burner or heat exchanger causing high back pressure
- Incorrect combustion settings
- Incoming gas pressure out of range
- Wrong boiler or altitude selected in the control
- Blocked flue or intake pipe
- Loose burner fasteners or gaskets
- Faulty venturi gaskets or wrong propane orifice
- Ignition cable resistance out of range
Test and repair steps
- Check the condensate trap for blockage and clear it.
- Inspect the igniter. Clean a fouled igniter with fine grit sandpaper or steel wool; replace a worn or badly fouled igniter.
- Set igniter rods parallel with a 3.5 mm (0.138 in) spark gap.
- Clean the burner and heat exchanger with the flue cleaning tool and rinse method in the maintenance section if they are dirty.
- Check combustion on high and low fire and adjust per setup instructions if needed.
- Check incoming gas pressure with the boiler off and at high fire. Keep within the limits on the rating label.
- Confirm the correct boiler model is selected in the control and high altitude is selected at 5,500 ft or above.
- Check the ignition cable resistance; it should read 1000 Ohms (±50 Ohms).
- Check the flue pipe and intake pipe for restrictions or blockage.
- Check burner fasteners, gaskets, venturi gaskets and propane orifice.
Other codes on the same units
- GAS PRESSURE SW FAULT Gas pressure switch open
- GAS VALVE FAULT Gas valve output circuit fault
- GV FAULT EXPANSION BRD Expansion board gas valve output fault
- HIGH TEMP LIMIT High temperature limit reached
- HW FAULT EXPANSION BRD Expansion control board hardware fault
- LIMIT OPEN External limit open
- LOW WTR CUTOFF OPEN Low water cutoff contacts open
- RETURN > SUPPLY Return temperature above supply
Sequence of operation
What the unit does around this code, step by step.
- Lighting and operating sequence · Startup
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Ultra Series 4 boiler manual, p. 122. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.