Weil-McLain · Boiler · Startup

Lighting and operating sequence

SVF Series 1

What happens, in order

  1. Set room thermostats to lowest setting.
  2. Turn OFF electrical power to the boiler.
  3. Remove the boiler access door.
  4. Turn the manual gas valve handle counterclockwise to open gas supply.
  5. Wait five minutes, then smell for gas near the floor. If gas is smelled, stop and follow the posted safety instructions.
  6. Turn ON electrical power.
  7. Set thermostat to desired setting.
  8. Watch the display as the boiler runs its operating sequence.
  9. If the boiler does not fire on a call for heat and piping is not warm, shut gas off and call service.
  10. Reinstall the access door and make sure it is seated.

Timings and thresholds

ItemValue
Wait before smelling for gas5 minutes

Codes you may see during this

Ignition Fault

Applies to: SVF 1500-3000

Models

SVF 1500SVF 2000SVF 2500SVF 3000

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 boiler manual, p. 91. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.