Weil-McLain · Boiler · Startup
Check flame and combustion with instruments
What happens, in order
- Call for heat on one thermostat input.
- Press and hold the WM logo at top left for 5 seconds on the Homeowner screen to enter installer menus.
- Confirm Max firing rate matches Figure 125 or 126 and adjust if needed.
- Go to DIAGNOSTICS, Manual test mode, and force HIGH fire.
- Look through the flame inspection window. High fire flame should be blue and stable, with the burner surface covered in orange dots.
- Remove the test port cap from the vent flue adapter and insert the combustion analyzer probe.
- Read CO2 (or O2) and CO. Compare with Figure 121.
- If readings are out of range, adjust the gas valve per the Gas Valve Adjustment section.
- Operate the boiler 10 minutes with other appliances off and measure gas input (see guide).
- Force LOW fire and check that the low fire flame is stable and evenly distributed with a uniform orange color.
- Repeat the combustion test at low fire.
- Force AUTO (normal operation).
- Reinstall the vent flue cap and confirm it is sealed.
Timings and thresholds
| Item | Value |
|---|---|
| Run boiler before gas input measurement | 10 minutes |
Applies to: ECO Tec Series 3 80/110/150/199
Models
80110150199
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist at commissioning · Startup
- Lighting and operating sequence · Startup
- Power-up and ignition sequence · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 133-136. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.