Weil-McLain · Boiler · Startup

Final verification checklist at commissioning

EGPEG

What happens, in order

  1. Confirm the boiler and heat distribution units are filled with water.
  2. Confirm any automatic air vent is open one full turn and air is purged from the system.
  3. Purge air from the gas piping and check the piping for leaks.
  4. Confirm the correctly sized manifold orifices are installed (Table 5, page 17).
  5. Follow the operating instructions and confirm a proper burner flame (see Check Burner Flames on page 60).
  6. Test the temperature limit. Burners should go off while the circulator runs and restart after the setting is raised above water temperature.
  7. Test the low water cutoff (LWCO). Burners should go off, the circulator should keep running, and LWCO should display.
  8. Test any field-installed low water cutoff, high limit or other controls. Burners should go off and restart when the controls are restored.
  9. Test the ignition system safety device by shutting off the gas at the manual main shutoff with the burners on.
  10. Set the Boiler Temp adjustment to the system requirement and adjust balancing valves and controls to deliver design temperature.
  11. Set Economy mode.
  12. On multiple zones, adjust flow so it is about equal in each zone.
  13. Cycle the boiler with the thermostat from highest to lowest setting and confirm normal start-up and shutdown.
  14. Cycle the DHW aquastat if used.
  15. Measure natural gas input.
  16. Check manifold gas pressure (3.5 in. w.c. for natural gas).
  17. Observe several operating cycles for proper operation.
  18. Set the room thermostat to the desired temperature.
  19. Complete the Installation and Service Certificate.
  20. Review the instructions with the owner or maintenance person and leave them with the owner.

Timings and thresholds

ItemValue
Run boiler before measuring gas input10 minutes

Applies to: EG and PEG Series 7 boilers at commissioning

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain EG/PEG Series 7 Boiler Manual, p. 65. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.