Weil-McLain · Boiler · Startup
Power-up and ignition sequence
What happens, in order
- At power-up, check that the boiler model on the power-up screen is correct. If it is wrong, turn the boiler off and change the setting (page 115).
- Confirm every sensor the control should see is listed on the power-up screen. If one is missing, check its wiring, turn power off and restart.
- In standby the display dots cycle; a wrench symbol replaces them when maintenance is due.
- On a call for heat, the display banner turns blue (space heating) or purple (DHW) and the blower goes to ignition speed for prepurge.
- After prepurge, the gas valve opens and the igniter sparks for the ignition period.
- Spark stops and the electrode checks for a flame signal.
Timings and thresholds
| Item | Value |
|---|---|
| Prepurge, ignition period | timed by the control; values not printed on these pages |
Applies to: ECO Tec Series 3 wall-mount gas condensing boilers
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist at commissioning · Startup
- Lighting and operating sequence · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 84. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.