Weil-McLain · Boiler · Startup

Closure switch interlock startup sequence

SVF Series 1

What happens, in order

  1. A call for heat closes an input contact.
  2. The corresponding output energizes, which may move the damper or shared device.
  3. The blower stays off until the closure switch makes.
  4. If the switch opens before ignition, the timer continues and the blower stays active.
  5. If the switch does not make within the allowed time, the control locks out.
  6. If the switch opens during burner firing, the control locks out.
  7. The output remains energized while the control tries to close the switch.

Timings and thresholds

ItemValue
Closure switch allowed time4 minutes

Applies to: Flow switch or CAD interlock

Models

SVF 1500SVF 2000SVF 2500SVF 3000

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 boiler manual, pp. 62-63. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.