Weil-McLain · Boiler · Startup
Check flame and combustion with instruments at high fire, low fire and auto
What happens, in order
- Call for heat on one heat demand input.
- Press and hold UP and DOWN arrow keys for five seconds to enter installer menus.
- Use the display to select Manual test mode and force firing rate to MAX (high fire).
- Look through the flame inspection window. High fire flame should be blue and stable, with orange dots over the burner surface.
- Pull the flue temperature sensor from the flue pipe and insert a calibrated combustion test probe.
- Test CO2 (or O2) and CO. CO2 must be within 1.0% of the Figure 42 value for the model and fuel. If not, adjust the throttle screw per the throttle screw procedure.
- Measure natural gas input run the boiler 10 minutes, turn off other appliances, time one cubic foot of gas at the meter in seconds, then calculate Btuh.
- Force firing rate to MIN (low fire) in Manual test mode. Flame should be stable, evenly spread and uniform orange.
- Repeat the combustion test at low fire.
- Force firing rate back to AUTO (normal operation).
- Replace the flue gas temperature sensor. Put the rubber grommet back into the flue pipe, then insert the probe into the grommet.
Timings and thresholds
| Item | Value |
|---|---|
| Run boiler before measuring gas input | 10 minutes |
Applies to: Ultra Series 4 gas-fired water boilers, all sizes, natural gas and propane
Models
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist at commissioning · Startup
- Lighting and operating sequence · Startup
- Power-up and ignition sequence · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 gas-fired water boiler manual, p. 40. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.