Weil-McLain · Boiler · Startup

Express Setup Example B wizard order (Combi with two zones)

ECO Tec Series 3

What happens, in order

  1. Choose SINGLE BOILER and press the right arrow.
  2. Accept the anti-scald valve confirmation, or disable DHW if none is installed.
  3. Verify the boiler model, sensor status and fuel type, altitude, units, WWSD temp and high temp limit.
  4. Set date and time, then press the right arrow.
  5. Press USE WIZARD.
  6. Set Combi enabled, hot water temp, max on time, preheat and eco boost.
  7. Set Input/Output 2 to heat demand, priority 2, system type and target settings.
  8. Set Input/Output 3 to heat demand, priority 3, system type and target settings.
  9. Finish the wizard and enter time, date and maintenance information when prompted.

Timings and thresholds

ItemValue
Hot water temp (Combi)120°F default example, up to 140°F
Combi max on time60 minutes
Zone max on time30 minutes
Zone min on time15 minutes
Target boost timeOFF

Applies to: ECO Tec Series 3 Combi with two zones

Models

ECO TEC 110 COMBI

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 100-104. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.