Weil-McLain · Boiler
LIMIT OPEN External limit open
What the control is telling you
A manual or automatic reset limit opened. Automatic external limit resets 2.5 minutes after the external limit closes. Manual limit must be reset from Reset Lockout on the display.
Applies to: Ultra Series 4 boilers
Likely causes
- External safety device has opened
- Loose wiring at the limit circuit
- Jumper missing at connector P13
Test and repair steps
- Check whether an external safety device is connected; if so, find and correct the cause that opened it.
- Check for loose wiring connections.
- Remove the top front cover and inspect the orange 4-pin connector P13.
- Make sure a jumper is between pins 1 and 2 if no manual reset external limit is used.
- Make sure a jumper is between pins 3 and 4 if no automatic reset external limit is used.
Other codes on the same units
- GAS VALVE FAULT Gas valve output circuit fault
- GV FAULT EXPANSION BRD Expansion board gas valve output fault
- HIGH TEMP LIMIT High temperature limit reached
- HW FAULT EXPANSION BRD Expansion control board hardware fault
- IGNITION FAULT No flame after 5 ignition attempts
- LOW WTR CUTOFF OPEN Low water cutoff contacts open
- RETURN > SUPPLY Return temperature above supply
- SUPPLY 58F > RETURN Supply temperature far above return
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Ultra Series 4 boiler manual, p. 121. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.