Weil-McLain · Boiler
SUPPLY 58F > RETURN Supply temperature far above return
What the control is telling you
Boiler outlet temperature is more than 58 °F above boiler inlet temperature while the burner is on. Resets automatically after a 30 second delay, or manually from the display.
Applies to: Ultra 80, 105, 155, 230, 299, 399
Likely causes
- Water flow through the boiler too low
- Piping not primary/secondary
- Circulator undersized or wrong size for the boiler
Test and repair steps
- Verify primary/secondary piping to the boiler loop (see Figure 4, page 11).
- Check minimum pipe sizes Ultra 80/105 1 in.; Ultra 155/230 1-1/4 in.; Ultra 299/399 1-1/2 in.
- Verify circulator sizing per page 10 and confirm the factory circulator is installed.
- If the TEMPERATURE SENSOR message also appears, check the sensors.
Other codes on the same units
- GV FAULT EXPANSION BRD Expansion board gas valve output fault
- HIGH TEMP LIMIT High temperature limit reached
- HW FAULT EXPANSION BRD Expansion control board hardware fault
- IGNITION FAULT No flame after 5 ignition attempts
- LIMIT OPEN External limit open
- LOW WTR CUTOFF OPEN Low water cutoff contacts open
- RETURN > SUPPLY Return temperature above supply
- TEMPERATURE SENSOR Temperature sensor short, open, or readings disagree
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Ultra Series 4 gas-fired water boiler manual, p. 119. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.