Weil-McLain · Boiler
SUPPLY 58° F > RETURN Supply exceeds return by 58°F
What the control is telling you
Boiler outlet temperature is more than 58°F above boiler inlet temperature. Auto reset after a 2 min 30 sec delay once the condition clears. The delay grows with each repeat while the burner runs under 2 minutes (2:30, 3:30, 4:30, 5:30, then 6:30), and resets once the burner runs longer than 2 minutes.
Applies to: SVF 1500-3000 Series 1 boiler
Likely causes
- Water piping not installed correctly
- Circulator wrong for boiler size or system
- Temperature sensor fault
Test and repair steps
- Verify water piping is installed per this manual.
- Verify circulator and speed match boiler size and system needs.
- Check sensors and connections as described under TEMPERATURE SENSOR FAULT.
Other codes on the same units
- LWCO GREEN Low water cutoff indicator green
- LWCO RED Low water cutoff indicator red
- NO DISPLAY - BOILER RUNNING Display blank while boiler is operating
- NO DISPLAY - NO 120V No display and no boiler components running, no 120V power
- NO DISPLAY - NO 24V No display, no 24V control power
- SUPPLY WATER TEMPERATURE TOO HIGH Supply temperature above 200°F while burner runs
- TEMPERATURE SENSOR FAULT Temperature sensor shorted or open
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain SVF Series 1 boiler manual, p. 104. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.