Weil-McLain · Boiler
SUPPLY WATER TEMPERATURE TOO HIGH Supply temperature above 200°F while burner runs
What the control is telling you
System supply temperature goes above 200°F with the burner running. Auto reset when supply drops below 200°F.
Applies to: SVF 1500-3000 Series 1 boiler
Likely causes
- Circulator flow direction wrong or circulator not pushing water through the system
Test and repair steps
- Verify the boiler circulator flow direction. It must push water through the system.
Other codes on the same units
- LWCO GREEN Low water cutoff indicator green
- LWCO RED Low water cutoff indicator red
- NO DISPLAY - BOILER RUNNING Display blank while boiler is operating
- NO DISPLAY - NO 120V No display and no boiler components running, no 120V power
- NO DISPLAY - NO 24V No display, no 24V control power
- SUPPLY 58° F > RETURN Supply exceeds return by 58°F
- TEMPERATURE SENSOR FAULT Temperature sensor shorted or open
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain SVF Series 1 boiler manual, p. 104. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.