Weil-McLain · Boiler
NO DISPLAY - BOILER RUNNING Display blank while boiler is operating
What the control is telling you
Display shows nothing but the boiler still runs. Communication from the control to the display is lost.
Applies to: SVF 1500-3000 Series 1 boiler
Likely causes
- Loose connection at the display plug or control board
- Faulty wire harness from display to control
- Failed display module
- Display contrast set wrong
Test and repair steps
- Check for loose connections and proper pin seating at plug P9, the Pump/Comm board P6 and J1, and the back of the display board.
- Check continuity on the harness from display to control.
- Cycle boiler power off and on and check operation.
- If still blank, replace the display module with the correct repair part.
- For contrast only power cycle, wait about 45 seconds, hold Enter and tap up or down to adjust. If that fails, replace the display.
Other codes on the same units
- LWCO GREEN Low water cutoff indicator green
- LWCO RED Low water cutoff indicator red
- NO DISPLAY - NO 120V No display and no boiler components running, no 120V power
- NO DISPLAY - NO 24V No display, no 24V control power
- SUPPLY 58° F > RETURN Supply exceeds return by 58°F
- SUPPLY WATER TEMPERATURE TOO HIGH Supply temperature above 200°F while burner runs
- TEMPERATURE SENSOR FAULT Temperature sensor shorted or open
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain SVF Series 1 boiler manual, p. 103. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.