Weil-McLain · Boiler
MANUAL LIMIT Manual-reset limit circuit open (includes rollout switch)
What the control is telling you
The manual-reset limit chain is open. The flame rollout switch is in this circuit, so a tripped rollout shows up as this fault.
Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)
Likely causes
- Factory jumper missing on the Manual Limit terminal block
- Field device in the manual limit chain open
- Rollout thermal switch open (flame rollout)
- Broken factory wiring back to the control
Test and repair steps
- Turn off power to the boiler before unplugging connectors or measuring resistance.
- A rollout trip means flame came out of the combustion area. Find out why (blocked flue passages, venting, overfire) before you put the boiler back on.
- No field devices on Manual Limit check the factory jumper and its wiring back to the control.
- Field devices wired in check continuity of the chain at the field wiring terminal blocks. Replace any device that will not close when it should.
- Check the rollout switch. The control cannot tell it apart from the rest of the chain, so test it on its own. An open rollout switch gets replaced.
Other codes on the same units
- HARDWARE FAULT 3 Control board hardware fault 3
- HARDWARE FAULT 4 Control board hardware fault 4
- HARDWARE FAULT 5 Pilot valve output fault (board or harness short)
- HARDWARE FAULT 6 Control board hardware fault 6
- HARDWARE FAULT 7 Main valve output fault (board or harness short)
- HARDWARE FAULT 8 Control board hardware fault 8
- LWCO Low water cutoff active / LWCO test
- SPILL SWITCH Spill switch open (flue gas spilling at the draft hood)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Table 11 Control fault information and troubleshooting, p.65. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.