Weil-McLain · Boiler

LWCO Low water cutoff active / LWCO test

High severity Weil-McLain CGa Series 4

What the control is telling you

The built-in low water cutoff in the temperature/LWCO sensor stops the burners when no water is sensed. Holding the LWCO TEST button does the same thing for testing; LWCO shows on the display while it is active.

Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)

Likely causes

  • LWCO TEST button being held (normal test)
  • Low water in the boiler (leak, relief valve discharge, bad fill)
  • Deposits on the sensor probe

Test and repair steps

  1. If you are testing burners should go off, the circulator keeps running and LWCO shows. Release the button and the ignition sequence should start again.
  2. Not testing check boiler pressure and water level. Find the cause of water loss before refilling.
  3. With low water and a call for heat the circulator only runs up to 15 minutes, then runs normally again once water is back.
  4. Check the LWCO status and reading in Diagnostics (WATER PRESENT / NO WATER).
  5. Clean the probe if needed (see the LWCO sensor guide).

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Component identification p.8; Final verification checklist p.56; Diagnostics LWCO menu p.46 and p.49. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.