LOW WTR CUTOFF OPEN Low water cutoff contacts open

High severity Ultra Series 4

What the control is telling you

Low water cutoff contacts have been open for more than 1 second. Needs a manual reset of the U-Control, and sometimes a manual reset of the LWCO device depending on model.

Applies to: Ultra 80, 105, 155, 230, 299, 399

Likely causes

  • Real low water condition in the system
  • LWCO wiring open or disconnected
  • Faulty low water cutoff device

Test and repair steps

  1. Check the system for low water and repair it (see the piping section).
  2. If there is no low water, check Diagnostics > Inputs for LWCO status.
  3. If the LWCO shows OPEN with water present, check the wiring between the LWCO and the U-Control.
  4. Reset the U-Control and the LWCO device if required.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Ultra Series 4 gas-fired water boiler manual, p. 120. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.