Weil-McLain · Boiler
LOW WTR CUTOFF OPEN Low water cutoff contacts open
What the control is telling you
Low water cutoff contacts have been open for more than 1 second. Needs a manual reset of the U-Control, and sometimes a manual reset of the LWCO device depending on model.
Applies to: Ultra 80, 105, 155, 230, 299, 399
Likely causes
- Real low water condition in the system
- LWCO wiring open or disconnected
- Faulty low water cutoff device
Test and repair steps
- Check the system for low water and repair it (see the piping section).
- If there is no low water, check Diagnostics > Inputs for LWCO status.
- If the LWCO shows OPEN with water present, check the wiring between the LWCO and the U-Control.
- Reset the U-Control and the LWCO device if required.
Other codes on the same units
- GAS VALVE FAULT Gas valve output circuit fault
- GV FAULT EXPANSION BRD Expansion board gas valve output fault
- HIGH TEMP LIMIT High temperature limit reached
- HW FAULT EXPANSION BRD Expansion control board hardware fault
- IGNITION FAULT No flame after 5 ignition attempts
- LIMIT OPEN External limit open
- RETURN > SUPPLY Return temperature above supply
- SUPPLY 58F > RETURN Supply temperature far above return
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Ultra Series 4 gas-fired water boiler manual, p. 120. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.