Weil-McLain · Boiler

RETURN > SUPPLY Return temperature above supply

Low severity Ultra Series 4

What the control is telling you

Return water temperature is 10 °F or more above the supply temperature. Applies to system sensors or boiler sensors. For system sensors the condition must last 10 minutes. Clears automatically when the condition ends.

Applies to: Ultra 80, 105, 155, 230, 299, 399

Likely causes

  • Boiler circulator running in the wrong direction
  • System sensors placed on the boiler loop
  • System sensors heated by nearby boiler piping

Test and repair steps

  1. Verify the boiler circulator pushes water through the boiler return pipe as shown in Figure 4, page 11.
  2. Confirm system sensors are on system piping, not on the boiler loop.
  3. If the boiler loop heats the sensors, move them farther from the boiler connection.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Ultra Series 4 gas-fired water boiler manual, p. 120. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.