Weil-McLain · Boiler
NO DISPLAY - NO 24V No display, no 24V control power
What the control is telling you
Display stays blank and the boiler does not answer a call for heat. The control is not getting 24V power.
Applies to: SVF 1500-3000 Series 1 boiler
Likely causes
- Short circuit or wrong wiring to the control
- Blown 3 A low-voltage fuse on the control
- Transformer not feeding 24VAC to the control
Test and repair steps
- Check wiring for shorts or errors against the wiring diagram, including transformer connection to the control.
- Check the 3 A low-voltage fuse on the control (page 100).
- Replace the fuse only with the specified part. If it blows again, recheck the wiring.
- Check for 24VAC output at the transformer.
- If the transformer has 120VAC in but no 24VAC out, replace the transformer.
Other codes on the same units
- LWCO GREEN Low water cutoff indicator green
- LWCO RED Low water cutoff indicator red
- NO DISPLAY - BOILER RUNNING Display blank while boiler is operating
- NO DISPLAY - NO 120V No display and no boiler components running, no 120V power
- SUPPLY 58° F > RETURN Supply exceeds return by 58°F
- SUPPLY WATER TEMPERATURE TOO HIGH Supply temperature above 200°F while burner runs
- TEMPERATURE SENSOR FAULT Temperature sensor shorted or open
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain SVF Series 1 boiler manual, p. 103. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.