Weil-McLain · Boiler

NO DISPLAY - NO 120V No display and no boiler components running, no 120V power

High severity SVF Series 1

What the control is telling you

Nothing shows on the display and no boiler components operate. The control is not getting line voltage.

Applies to: SVF 1500-3000 Series 1 boiler

Likely causes

  • Service switch or circuit breaker to the boiler is off
  • No 120VAC supply to the service switch
  • Wiring fault inside the control pod
  • Blown 12 A line-voltage fuse

Test and repair steps

  1. Confirm the service switch and/or breaker is on.
  2. Check for 120VAC at the service switch. If absent, fix the supply to the switch.
  3. Check for 120VAC at the line voltage terminal block in the top left electrical compartment.
  4. Correct wiring inside the control pod using the wiring diagram.
  5. Inspect the 12 A line-voltage fuse (page 100) and replace with the specified part if needed. If it blows again, recheck wiring.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain SVF Series 1 boiler manual, p. 103. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.