Weil-McLain · Boiler

TEMPERATURE SENSOR FAULT Temperature sensor shorted or open

Medium severity SVF Series 1

What the control is telling you

A temperature sensor is shorted or disconnected. Auto reset if the condition clears.

Applies to: SVF 1500-3000 Series 1 boiler

Likely causes

  • Sensor shorted or open
  • Loose or bad connection at sensor, chassis mount or control
  • Faulty control

Test and repair steps

  1. Check all boiler temperatures on DIAGNOSTICS - TEMPERATURES for SHORT or OPEN readings.
  2. Compare against temperatures in DIAGNOSTICS - ERRORS - LOCKOUT HISTORY # - TEMPERATURES.
  3. Measure suspect sensor resistance and compare to the sensor table (page 101).
  4. If resistance is wrong, replace the sensor using the repair parts section.
  5. Check harness for loose connections and pin engagement at sensor, chassis mount and control. Unplug and check continuity end to end.
  6. If the fault persists, replace the control (see repair parts section for kit number).

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain SVF Series 1 boiler manual, p. 104. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.