TEMPERATURE SENSOR FAULT Temperature sensor shorted or open
What the control is telling you
A temperature sensor is shorted or disconnected. Auto reset if the condition clears.
Applies to: SVF 1500-3000 Series 1 boiler
Likely causes
- Sensor shorted or open
- Loose or bad connection at sensor, chassis mount or control
- Faulty control
Test and repair steps
- Check all boiler temperatures on DIAGNOSTICS - TEMPERATURES for SHORT or OPEN readings.
- Compare against temperatures in DIAGNOSTICS - ERRORS - LOCKOUT HISTORY # - TEMPERATURES.
- Measure suspect sensor resistance and compare to the sensor table (page 101).
- If resistance is wrong, replace the sensor using the repair parts section.
- Check harness for loose connections and pin engagement at sensor, chassis mount and control. Unplug and check continuity end to end.
- If the fault persists, replace the control (see repair parts section for kit number).
Other codes on the same units
- LWCO GREEN Low water cutoff indicator green
- LWCO RED Low water cutoff indicator red
- NO DISPLAY - BOILER RUNNING Display blank while boiler is operating
- NO DISPLAY - NO 120V No display and no boiler components running, no 120V power
- NO DISPLAY - NO 24V No display, no 24V control power
- SUPPLY 58° F > RETURN Supply exceeds return by 58°F
- SUPPLY WATER TEMPERATURE TOO HIGH Supply temperature above 200°F while burner runs
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain SVF Series 1 boiler manual, p. 104. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.