Weil-McLain · Boiler

TEMPERATURE SENSOR Temperature sensor short, open, or readings disagree

Medium severity Ultra Series 4

What the control is telling you

Covers two conditions with the same message: a sensor is shorted or disconnected (SHORT or OPEN), or dual sensor readings differ by more than 10 °F. Clears automatically when the condition ends. Optional outdoor and system sensors always show OPEN when not installed, which is normal.

Applies to: Ultra 80, 105, 155, 230, 299, 399

Likely causes

  • Shorted or open sensor
  • Loose connection or poor pin engagement in the harness
  • Failed U-Control module
  • Dual sensors reading more than 10 °F apart

Test and repair steps

  1. On Diagnostics > Temperatures, check which sensors show SHORT or OPEN.
  2. Compare with lockout history temperatures in Diagnostics > Errors.
  3. Measure suspect sensor resistance and compare with Figure 123 (page 116); replace the sensor if values are wrong.
  4. If dual sensors differ by more than 10 °F when converted, replace the sensor.
  5. Check the harness at the sensor, the chassis connection and the U-Control; check continuity end to end.
  6. If the problem remains, replace the U-Control (kit number in the repair parts section).

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Ultra Series 4 gas-fired water boiler manual, p. 120. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.