Weil-McLain · Boiler

TEMP RISE TOO QUICKLY Supply water temperature rising too fast

High severity ECO Tec series 3

What the control is telling you

Occurs if supply water in the heat exchanger rises faster than 10F per second for two seconds during the first two minutes of burner operation. Resets automatically after a one minute delay or by manual reset on the display. After 5 automatic resets during the same priority heat demand, a manual reset is required.

Applies to: ECO Tec series 3 80/110/150/199

Likely causes

  • Water piping not installed per manual
  • Circulator wrong for boiler size or system
  • Loose temperature sensor connection

Test and repair steps

  1. Verify water piping is installed per the instructions in this manual.
  2. Verify the circulator and its speed suit the boiler size and system.
  3. Follow the TEMPERATURE SENSOR message procedure for loose connections.
  4. Use the manual reset screen on the display if five automatic resets have occurred.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 168. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.