Weil-McLain · Boiler

Target Reduced - Flue Target reduced for high flue temperature

Normal status ECO Tec series 3

What the display is showing

Flue temperature is between 200F and 210F. The target is lowered to prevent overheating the flue. Clears after flue has stayed below 200F, the target has returned to its setpoint, and one hour of burner run time has passed without the flue exceeding 200F.

Applies to: ECO Tec series 3 80/110/150/199

Good to know

  • Flue blockage
  • CO2 out of nominal range

What to do

  1. Check the flue pipe for blockages.
  2. Check CO2 with an analyzer and adjust the gas valve to bring CO2 within the nominal range in this manual.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 168. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.