Weil-McLain · Boiler
Target Reduced - Flue Target reduced for high flue temperature
What the display is showing
Flue temperature is between 200F and 210F. The target is lowered to prevent overheating the flue. Clears after flue has stayed below 200F, the target has returned to its setpoint, and one hour of burner run time has passed without the flue exceeding 200F.
Applies to: ECO Tec series 3 80/110/150/199
Good to know
- Flue blockage
- CO2 out of nominal range
What to do
- Check the flue pipe for blockages.
- Check CO2 with an analyzer and adjust the gas valve to bring CO2 within the nominal range in this manual.
Other codes on the same units
- Software Incompatible Main control and display software mismatch
- Supply 60F > Return Supply more than 60F above return (soft lockout)
- System Return > Supply System return hotter than system supply
- TEMP RISE TOO QUICKLY Supply water temperature rising too fast
- Target Reduced - Boiler Target reduced because boiler outlet is near max temperature
- Target Reduced - Flow Target reduced for low water flow across heat exchanger
- Unconfigured Net 1 or Net 2 Demand Net 1 or Net 2 input active but not configured
- Virtual Input Active Modbus commanding a virtual TT input
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: ECO Tec Series 3 boiler manual, p. 168. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.