Weil-McLain · Boiler

System Return > Supply System return hotter than system supply

Medium severity ECO Tec series 3

What the control is telling you

Occurs when system return is more than 10F above system supply, after the burner has run 10 minutes and the priority has not changed in the last 10 minutes. Clears automatically.

Applies to: ECO Tec series 3 80/110/150/199

Likely causes

  • System sensors mounted on the boiler loop instead of system piping
  • Sensors wired to the wrong terminals
  • Sensors heated by proximity to the boiler loop connection

Test and repair steps

  1. Place system sensors on system piping, not on the boiler loop.
  2. Verify sensors are wired to the correct terminal locations.
  3. Move system sensors farther from the boiler loop connection if they are being heated by it.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 168. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.