Weil-McLain · Boiler
Target Reduced - Flow Target reduced for low water flow across heat exchanger
What the display is showing
Boiler outlet sensor reads more than 50F above boiler inlet sensor. The control lowers the target to protect the heat exchanger. Clears when outlet is within 50F of inlet.
Applies to: ECO Tec series 3 80/110/150/199
Good to know
- Poor water flow through the boiler heat exchanger
- Circulator malfunction or wiring problem
What to do
- Check water flow through the boiler heat exchanger.
- Check circulators for malfunction or wiring issues.
Other codes on the same units
- Software Incompatible Main control and display software mismatch
- Supply 60F > Return Supply more than 60F above return (soft lockout)
- System Return > Supply System return hotter than system supply
- TEMP RISE TOO QUICKLY Supply water temperature rising too fast
- Target Reduced - Boiler Target reduced because boiler outlet is near max temperature
- Target Reduced - Flue Target reduced for high flue temperature
- Unconfigured Net 1 or Net 2 Demand Net 1 or Net 2 input active but not configured
- Virtual Input Active Modbus commanding a virtual TT input
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: ECO Tec Series 3 boiler manual, p. 168. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.