Weil-McLain · Boiler

Supply 60F > Return Supply more than 60F above return (soft lockout)

High severity ECO Tec series 3

What the control is telling you

Shows when boiler outlet is more than 60F above boiler inlet, or when the burner has run less than 2 minutes. If it happens after 2 minutes of burner run, the burner stops with no message. Lockout times rise each time: 2 min 30 s, 3 min 30 s, 4 min 30 s, 5 min 30 s, then 6 min 30 s. After that the system retries every 6 min 30 s while temperatures stay under the limit. Two minutes of firing without exceeding 60F resets the timer to 2 min 30 s.

Applies to: ECO Tec series 3 80/110/150/199

Likely causes

  • Insufficient water flow through the boiler
  • Circulators undersized or incorrectly installed
  • Circulator wiring fault

Test and repair steps

  1. Make sure proper water flow is present through the boiler.
  2. Confirm circulators are sized correctly for the system and installed correctly.
  3. Check wiring to the circulators.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 168. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.