Weil-McLain · Boiler

SPILL SWITCH Spill switch open (flue gas spilling at the draft hood)

Critical severity Weil-McLain CGa Series 4

What the control is telling you

The spill switch on the draft hood opened, usually because the vent is blocked or wind is pushing flue gas back. The switch has its own manual reset button.

Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)

Likely causes

  • Blocked or restricted vent or chimney
  • Down draft from wind
  • Failed spill switch

Test and repair steps

  1. Flue gas spilling means a carbon monoxide risk. Check the chimney/vent for blockage and draft before you reset anything.
  2. Check the spill switch for continuity.
  3. Open press the reset button on the switch.
  4. Still open after reset replace the switch (210°F switch, part 510-300-013 per the parts list).

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Table 11 Control fault information and troubleshooting, p.67 (parts p.70). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.