Weil-McLain · Boiler

FLUE TEMP TOO HIGH Flue gas temperature too high

High severity Ultra Series 4

What the control is telling you

Flue sensor is above 216 °F. Resets automatically if the flue temperature drops below 216 °F for 2.5 minutes. Manual reset is required if it rises above 225 °F.

Applies to: Ultra 80, 105, 155, 230, 299, 399

Likely causes

  • Fouled or worn heat exchanger combustion chamber or flueways
  • Damaged or obstructed vent system
  • Faulty flue sensor

Test and repair steps

  1. Check the flue sensor using the SHORT/OPEN sensor procedure (see TEMPERATURE SENSOR).
  2. Inspect the heat exchanger combustion chamber and flueways for abnormal wear or buildup.
  3. Inspect the vent system for abnormal wear or damage.
  4. If the fault stays, contact WM Technologies Technical Support.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Ultra Series 4 gas-fired water boiler manual, p. 120. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.