Weil-McLain · Boiler

AUTO LIMIT Auto-reset limit circuit open

Medium severity Weil-McLain CGa Series 4

What the control is telling you

The automatic-reset limit chain wired to P4 is open. The boiler resets on its own once the circuit closes again.

Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)

Likely causes

  • Factory jumper missing or broken on the Auto Limit terminal block
  • Field device in the auto limit chain open (external limit, extra LWCO, etc.)
  • Loose P4 connector or broken factory wire to the control
  • Faulty control

Test and repair steps

  1. Turn off power to the boiler before unplugging connectors or measuring resistance.
  2. No field devices on Auto Limit make sure the factory jumper is there and has continuity back to the control. Put it back if it was removed.
  3. Field devices wired in check continuity across P4 pins 2 and 3.
  4. No continuity check each device. A device that stays open when conditions say it should be closed gets replaced.
  5. Continuity is good check the factory wiring and make sure P4 is fully seated.
  6. Still shows Auto Limit open with a good circuit: replace the control.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Table 11 Control fault information and troubleshooting, p.64. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.