L1 POLARITY Line voltage polarity reversed
What the control is telling you
The control is polarity-sensitive. With hot and neutral reversed on the 120 VAC supply it shows FAULT L1 POLARITY and will not run the boiler.
Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)
Likely causes
- Hot and neutral swapped at the service switch, junction box or outlet
Test and repair steps
- Turn off power at the service switch.
- Check the 120 VAC supply wiring and swap hot and neutral to the correct terminals.
- Restore power and confirm the fault clears and the boiler cycles.
Other codes on the same units
- AUTO LIMIT Auto-reset limit circuit open
- BOILER OUT OPEN Boiler outlet sensor open circuit
- BOILER OUT SHORT Boiler outlet sensor shorted
- CH VOLTAGE HIGH Too much voltage on the CH / Thermostat 1 input
- CONFIG MISMATCH Stored configuration does not match the harness
- CONFIGURATION Control board not configured
- DHW VOLTAGE HIGH Too much voltage on the DHW / Thermostat 2 input
- FALSE FLAME Flame sensed when the gas valve is off
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Spark-ignited pilot system notes, p.38. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.