L1 POLARITY Line voltage polarity reversed

Medium severity Weil-McLain CGa Series 4

What the control is telling you

The control is polarity-sensitive. With hot and neutral reversed on the 120 VAC supply it shows FAULT L1 POLARITY and will not run the boiler.

Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)

Likely causes

  • Hot and neutral swapped at the service switch, junction box or outlet

Test and repair steps

  1. Turn off power at the service switch.
  2. Check the 120 VAC supply wiring and swap hot and neutral to the correct terminals.
  3. Restore power and confirm the fault clears and the boiler cycles.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Spark-ignited pilot system notes, p.38. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.