Lennox furnace error codes
202 codes (177 faults, 25 normal display and menu codes), plus 5 settings tables.
| Code | Meaning | Severity / type |
|---|---|---|
| 1 flash | Line voltage polarity reversed | Medium |
| 2 flashes | Improper earth ground | Medium |
| 3 flashes | Burner failed to light or lost flame | High |
| 4 flashes | Low flame signal | Medium |
| 5 flashes | Watchguard - ignition retries/recycles exceeded | High |
| 7 flashes | Primary or secondary limit open | High |
| 8 flashes | Rollout switch open | Critical |
| 9 flashes | Pressure switch stays open or drops out on a heat call | High |
| 10 | Unknown device detected | High |
| 10 flashes | Watchguard - pressure switch opened 5 times in one heat demand | High |
| 11 | Missing device | High |
| 11 flashes | Pressure switch stuck closed before inducer starts | Medium |
| 12 | Indoor unit not detected | High |
| 12 flashes | Flame sensed with gas valve off | Critical |
| 13 | Duplicate comfort sensor ID | High |
| 13 flashes | Low line voltage | Medium |
| 14 | Too many devices of the same type | High |
| 15 | Parameter mismatch detected | Low |
| 20 | Protocol upgrade required | High |
| 21 | Incompatible equipment detected | High |
| 29 | Over temperature protection (indoor above 90 F) | High |
| 30 | Low temperature protection (below 40 F) | High |
| 31 | Lost communication with device | High |
| 32 | Device resetting | Low |
| 34 | Must program unit capacity for device | High |
| 40 | HP heating lockout | Low |
| 41 | Device control board replaced | Low |
| 500 | PureAir differential pressure sensor fault | Medium |
| 501 | PureAir UV sensor fault | Medium |
| 502 | PureAir UV lamp off | Medium |
| 503 | PureAir filter life at 10% | Medium |
| 504 | PureAir filter life at 0% | Medium |
| 505 | PureAir model selection changed | Medium |
| 506 | PureAir lamp at 0% life | Medium |
| 507 | PureAir filter calibration failure | Medium |
| 530 | Zoning low damper 24 VAC | Medium |
| 532 | Zoning pressure switch opened (high pressure) | Low |
| 542 | Zone 1 temperature sensor fault | Medium |
| 543 | Zone 2 temperature sensor fault | Medium |
| 544 | Zone 3 temperature sensor fault | Medium |
| 545 | Zone 4 temperature sensor fault | Medium |
| 546 | Zone sensor parameters reset after power restore | Medium |
| 547 | Zone sensor parameters reset from system interruption | Medium |
| 548 | Zone humidity sensor error | Medium |
| 551 | Zone sensor lost communication | Medium |
| 610 | Low room temperature detected | High |
| 700 | Thermostat temperature sensor problem | High |
| 701 | Thermostat temperature above limit | High |
| 703 | Thermostat humidity sensor problem | Medium |
| 3000 | Replace filter 1 | Low |
| 3001 | Replace filter 2 | Low |
| 3002 | Replace humidifier pad | Low |
| 3003 | Replace UV bulb | Low |
| 3004 | Maintenance reminder | Low |
| 3005 | PureAir maintenance | Low |
| 65537 | Missing base (smart hub) | High |
| 65538 | Missing base | Low |
| 65539 | Thermostat lost connection or internal fault | High |
| 65540 | Missing HD wall display | Low |
| 65541 | Firmware download failed | Low |
| 65542 | Firmware update failed | Low |
| 65543 | Firmware updated | Low |
| 65544 | More than 8 thermostats in a group | Low |
| 70001 | IAQ internal sensor fault | Medium |
| 70002 | IAQ internal data fault | Medium |
| 70003 | IAQ side switch in OFF position | High |
| 70004 | Replace Smart IAQ monitor | Medium |
| 70501 | Smart room sensor internal data fault | Medium |
| 70502 | Smart room sensor internal fault | Medium |
| 70503 | Smart room sensor low battery | Low |
| 70504 | Smart room sensor battery 1% | Low |
| 71001 | Wireless extender internal data fault | Medium |
| 71511 | Duct or filter blockage | Medium |
| 71517 | Indoor fan motor failure | High |
| 80001 | IAQ persistent poor air quality | Low |
| 80002 | Unresponsive wireless device fault | Low |
| 80003 | Lost communication with wireless device | Medium |
| 80005 | Unknown wireless device found | Medium |
| C1 | Cooling, stage 1 | Normal status |
| C2 | Cooling, stage 2 | Normal status |
| E000 | No error in memory | Normal status |
| E105 | Device communication problem | High |
| E106 | Twin communication fault | Medium |
| E110 | Low line voltage | High |
| E111 | Line voltage polarity reversed | High |
| E112 | Ground not detected | High |
| E113 | High line voltage | High |
| E114 | Line frequency out of range | High |
| E115 | Low 24 VAC | High |
| E116 | High 24 VAC | High |
| E117 | Poor ground detected | Medium |
| E120 | Unresponsive device | Medium |
| E124 | Lost communication with thermostat | High |
| E125 | Control hardware failure | Critical |
| E126 | Control internal communication problem | High |
| E130 | Configuration jumper missing | High |
| E131 | Corrupted control parameters | High |
| E132 | Device control software fault | High |
| E150 | A2L refrigerant leak alarm | Critical |
| E151 | A2L sensor fault | High |
| E152 | Refrigerant leak sensor #2 fault | High |
| E154 | Refrigerant leak sensor #1 communication lost / wrong DIP setting | High |
| E155 | Refrigerant leak sensor #2 communication lost | High |
| E160 | Refrigerant leak sensor #1 wrong type | Medium |
| E161 | Refrigerant leak sensor #2 wrong type | Medium |
| E163 | Furnace control board failure | High |
| E164 | Low GWP test mode active | Low |
| E180 | Outdoor air temperature sensor failure | Medium |
| E200 | Flame rollout - hard lockout | Critical |
| E201 | Indoor blower communication failure | High |
| E202 | Blower motor mismatch | High |
| E203 | Unit capacity not programmed | Critical |
| E204 | Gas valve miswired | High |
| E205 | Gas valve relay contact shorted | Critical |
| E206 | Gas valve second-stage relay failure | Medium |
| E207 | Hot surface ignitor open | High |
| E223 | Low pressure switch failed open | High |
| E224 | Low pressure switch failed closed | High |
| E225 | High pressure switch failed open | High |
| E226 | High pressure switch failed closed | High |
| E227 | Low pressure switch opened during ignition or run | High |
| E228 | Inducer calibration failure | Medium |
| E229 | Ignition on high fire | Low |
| E240 | Low flame current (run mode) | Medium |
| E241 | Flame sensed out of sequence - flame present | Critical |
| E250 | Limit switch circuit open | High |
| E252 | Discharge air temperature too high | Medium |
| E270 | Soft lockout - no flame after max retries | High |
| E271 | Soft lockout - retries exceeded, pressure switch opened | High |
| E272 | Soft lockout - recycles exceeded, pressure switch opened | High |
| E273 | Soft lockout - recycles exceeded, flame failure | High |
| E274 | Soft lockout - limit opened | High |
| E275 | Soft lockout - flame out of sequence, now gone | Critical |
| E276 | Watchguard calibration failure | High |
| E290 | Ignitor circuit fault | High |
| E291 | Heat airflow below minimum | High |
| E292 | Blower motor will not start | High |
| E294 | Inducer over current | High |
| E295 | Blower motor over temperature | High |
| E310 | Discharge air sensor failure | Medium |
| E311 | Heat rate reduced for airflow | Medium |
| E312 | Restricted airflow in cooling/fan | Medium |
| E313 | Indoor/outdoor capacity mismatch | Low |
| E331 | Global network connection problem | Low |
| E334 | Y1 relay stuck on control | High |
| E344 | IFC relay Y1 stuck | High |
| E345 | Relay O failure | High |
| E347 | No 24 V on Y1 output | Critical |
| E348 | No 24 V on Y2 output | Critical |
| E349 | No 24 V between R and O | Critical |
| E370 | Interlock switch open | High |
| E380 | EIM interlock relay fault | High |
| E381 | EIM interlock relay stuck | High |
| E382 | EIM relay W1 fault | High |
| E390 | Low GWP relay stuck | High |
| E400 | LSOM - compressor internal overload | High |
| E401 | LSOM - long run or low pressure | Critical |
| E402 | LSOM - outdoor pressure trip | High |
| E403 | LSOM - compressor short cycling | Medium |
| E404 | LSOM - locked rotor | High |
| E405 | LSOM - compressor open circuit | High |
| E406 | LSOM - open start circuit | High |
| E407 | LSOM - open run circuit | High |
| E408 | LSOM - welded contactor | High |
| E409 | LSOM - low secondary voltage | High |
| H1 | Gas heat, stage 1 (low fire) | Normal status |
| H2 | Gas heat, stage 2 (high fire) | Normal status |
| LED1 & LED2 alternating FAST flash | Improper ground, broken ignitor, open ignitor circuit or low line voltage | High |
| LED1 & LED2 alternating SLOW flash | Watchguard lockout - burners failed to ignite or repeated failures | High |
| LED1 & LED2 simultaneous FAST flash | Normal - heat call in progress | Normal status |
| LED1 & LED2 simultaneous SLOW flash | Normal - power on, idle, cooling or continuous fan | Normal status |
| LED1 FAST flash / LED2 SLOW flash | 120 V line and neutral reversed | High |
| LED1 OFF / LED2 OFF | No power to the control | High |
| LED1 OFF / LED2 ON | Control board failure or control wired incorrectly | High |
| LED1 OFF / LED2 SLOW flash | Prove switch (pressure switch) open | High |
| LED1 ON / LED2 OFF | Control board failure or control wired incorrectly | High |
| LED1 ON / LED2 ON | Control board failure or control wired incorrectly | High |
| LED1 ON / LED2 SLOW flash | Rollout switch open | Critical |
| LED1 SLOW flash / LED2 FAST flash | Low flame signal | Medium |
| LED1 SLOW flash / LED2 OFF | Flame sensed with gas valve not energized | Critical |
| LED1 SLOW flash / LED2 ON | Primary or secondary limit open | High |
| -- | Double dashes - zone sensor problem | Medium |
| . | Idle - no call | Normal status |
| = | Two bars - soft disable | Menu / mode display |
| A | Blower airflow setting | Normal status |
| E | Error recall mode (button menu) | Menu / mode display |
| F | Flame signal mode (button menu) | Menu / mode display |
| Green LED 3 s on / 1 s off | Soft disable - zoning damper module or EIM | Menu / mode display |
| LGWP Test button | Low GWP refrigerant detection board: modes and Test button | Menu / mode display |
| P | Program unit size (button menu) | Menu / mode display |
| Power-up size code | Unit size code shown at power-up (variable speed) | Menu / mode display |
| Red LED fast flash (heartbeat) | Call for heat - burner operation | Normal status |
| Red LED off | No power to control or board fault | High |
| Red LED on steady | Board fault detected (107163-01) | High |
| Red LED recall button | Error recall button on the ignition control | Menu / mode display |
| Red LED slow flash (heartbeat) | Normal - idle, continuous fan or cooling | Normal status |
| U | Discharge air temperature | Normal status |
| c | Clear stored errors (inside error recall) | Menu / mode display |
| d | Dehumidification mode | Normal status |
| dF | Defrost mode | Normal status |
| h | Heat pump stage (dual fuel) | Normal status |
| ≡ | Three bars - back to normal | Menu / mode display |
Settings and specs
Recommended filter size by cabinet width
Filters · EL296UHV
| Cabinet width | Side return | Bottom return |
|---|---|---|
| 17-1/2 in. | 16 x 25 x 1 in. (1) | 16 x 25 x 1 in. (1) |
| 21 in. | 16 x 25 x 1 in. (1) | 20 x 25 x 1 in. (1) |
| 24-1/2 in. | 16 x 25 x 1 in. (2) | 24 x 25 x 1 in. (1) |
- Number in brackets is the quantity of filters.
- Filters are field supplied and installed outside the furnace; inspect monthly.
- High-efficiency filters add static pressure; size them so total static stays within limits.
- On 090XV60C, 110XV60C and 135XV60D single side return, high airflows need the return air base and a transition to a 20 x 25 x 1 in. filter.
Source: Lennox EL296UHV(X) Unit Information, Corp 1125-L5 (rev. 03/2022), Table 34 filter sizes, p.88 (printed p.87); blower data notes p.18-26
Recommended filter size by cabinet width
Filters · Lennox SL280UHV
| Cabinet width | Side return | Bottom return |
|---|---|---|
| 14-1/2 in. | 16 x 25 x 1 in. (1) | 14 x 25 x 1 in. (1) |
| 17-1/2 in. | 16 x 25 x 1 in. (1) | 16 x 25 x 1 in. (1) |
| 21 in. | 16 x 25 x 1 in. (1) | 20 x 25 x 1 in. (1) |
| 24-1/2 in. | 16 x 25 x 1 in. (2) | 24 x 25 x 1 in. (1) |
- Number in brackets is filter quantity; filters are field supplied.
- Never run the unit without a filter installed.
- 60C/60D sizes needing over 1800 cfm: use bottom return, both sides, bottom + one side, or single side with return air base and 20 x 25 x 1 in. filter.
- Cabinet A width: 070V36A 14 in. (manual), 090V36B/090V48B 17-1/2 in., 090V60C/110V60C 21 in., 135V60D 24-1/2 in.
Source: Lennox SL280UHV Installation Instructions 508245-01 (04/2024), Table 1 p.12; Unit Dimensions p.2
Filter sizes by cabinet width
Filters · Lennox ML180UHE
| Cabinet | Side return | Bottom return |
|---|---|---|
| A - 14-1/2 in. | 16 x 25 x 1 (1) | 14 x 25 x 1 (1) |
| B - 17-1/2 in. | 16 x 25 x 1 (1) | 16 x 25 x 1 (1) |
| C - 21 in. | 16 x 25 x 1 (1) | 20 x 25 x 1 (1) |
| D - 24-1/2 in. | 16 x 25 x 1 (2) | 24 x 25 x 1 (1) |
- Filters are field supplied; check monthly.
- Cabinet letter is the letter after the cooling size in the model number: A = 045E36AK, 070E36AK; B = 070E36BK, 090E48BK; C = 090E60CK, 110E60CK; D = 135E60DK.
Source: Lennox ML180UHEK Unit Information 100161/100166, Table 16, p.30
Filter sizes (filter rack kits)
Filters · Lennox EL195UHNE
| Cabinet | Horizontal end rack | Side return rack |
|---|---|---|
| B width (040, 060) | 18 x 25 x 1 (kit 87L96) | 16 x 25 x 1 (kit 44J22) |
| C width (080, 100) | 20 x 25 x 1 (kit 87L97) | 16 x 25 x 1 (kit 44J22) |
- Filters are field supplied; check monthly.
- 100NE60C over 1800 cfm with single side return needs a 20 x 25 x 1 filter via return air base and transition.
Source: Lennox EL195UHNE Unit Information Corp 1801-L1 (rev 04/2024), Optional Accessories, p.3
Filter sizes by cabinet width
Filters · Lennox SL297NV
| Cabinet | Side return | Bottom return |
|---|---|---|
| 17-1/2 in. (040, 060) | 16 x 25 x 1 (1) | 16 x 25 x 1 (1) |
| 21 in. (080) | 16 x 25 x 1 (1) | 20 x 25 x 1 (1) |
- No filter or rack supplied; use a field high-velocity rated filter and keep one in place whenever the unit runs.
Source: Lennox SL297UHNV Installation Instructions 507760-02 (02/2018), Table 1, p.11
Models covered
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.