Lennox · Furnace
LGWP Test button Low GWP refrigerant detection board: modes and Test button
What the display is showing
The ML180UHEK control has a Test/Reset button for the refrigerant leak (Low GWP) function. The board is always in one of four modes: Initializing (linking to the sensor and running a 5-minute purge), Normal (no leak detected), Leak Detected, or Fault. In Normal mode a press forces a simulated leak response, which shows code E164 for about a minute. In Leak Detected or Fault mode a press resets the board once the problem is fixed. A long press resets the control; a short press while initializing skips the rest of the pre-purge.
Applies to: Lennox ML180UHEK furnaces with Low GWP refrigerant detection control board
What to do
- To test after installation restore power and wait for the initializing purge to finish.
- Start a cooling or heating call and press the Test button; the blower should start, the compressor should stop (and the burners on a heat call).
- Press Test again to end the simulated leak.
- After a real leak or fault is resolved, press Test to bring the board back to Normal.
Settings for these units
Filter sizes by cabinet width · Lennox ML180UHE
| Cabinet | Side return | Bottom return |
|---|---|---|
| A - 14-1/2 in. | 16 x 25 x 1 (1) | 14 x 25 x 1 (1) |
| B - 17-1/2 in. | 16 x 25 x 1 (1) | 16 x 25 x 1 (1) |
| C - 21 in. | 16 x 25 x 1 (1) | 20 x 25 x 1 (1) |
| D - 24-1/2 in. | 16 x 25 x 1 (2) | 24 x 25 x 1 (1) |
Filters are field supplied; check monthly.
Cabinet letter is the letter after the cooling size in the model number: A = 045E36AK, 070E36AK; B = 070E36BK, 090E48BK; C = 090E60CK, 110E60CK; D = 135E60DK.
Models that show this code
12 models in Lennox ML180UHE
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox ML180UHEK 100166, Furnace Control Board Low GWP Modes of Operation and LGWP Test Button Functionality (Tables 18-19), printed p.34-35. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.