Lennox · Furnace

LGWP Test button Low GWP refrigerant detection board: modes and Test button

Menu / mode display Lennox ML180UHE

What the display is showing

The ML180UHEK control has a Test/Reset button for the refrigerant leak (Low GWP) function. The board is always in one of four modes: Initializing (linking to the sensor and running a 5-minute purge), Normal (no leak detected), Leak Detected, or Fault. In Normal mode a press forces a simulated leak response, which shows code E164 for about a minute. In Leak Detected or Fault mode a press resets the board once the problem is fixed. A long press resets the control; a short press while initializing skips the rest of the pre-purge.

Applies to: Lennox ML180UHEK furnaces with Low GWP refrigerant detection control board

What to do

  1. To test after installation restore power and wait for the initializing purge to finish.
  2. Start a cooling or heating call and press the Test button; the blower should start, the compressor should stop (and the burners on a heat call).
  3. Press Test again to end the simulated leak.
  4. After a real leak or fault is resolved, press Test to bring the board back to Normal.

Settings for these units

Filter sizes by cabinet width · Lennox ML180UHE

CabinetSide returnBottom return
A - 14-1/2 in.16 x 25 x 1 (1)14 x 25 x 1 (1)
B - 17-1/2 in.16 x 25 x 1 (1)16 x 25 x 1 (1)
C - 21 in.16 x 25 x 1 (1)20 x 25 x 1 (1)
D - 24-1/2 in.16 x 25 x 1 (2)24 x 25 x 1 (1)

Filters are field supplied; check monthly.

Cabinet letter is the letter after the cooling size in the model number: A = 045E36AK, 070E36AK; B = 070E36BK, 090E48BK; C = 090E60CK, 110E60CK; D = 135E60DK.

Models that show this code

12 models in Lennox ML180UHE

ML180UH045E36AKML180UH045XE36AKML180UH070E36AKML180UH070E36BKML180UH070XE36AKML180UH070XE36BKML180UH090E48BKML180UH090E60CKML180UH090XE48BKML180UH110E60CKML180UH110XE60CKML180UH135E60DK

Other codes on the same units

  • . Idle - no call
  • E Error recall mode (button menu)
  • F Flame signal mode (button menu)
  • c Clear stored errors (inside error recall)
  • d Dehumidification mode
  • dF Defrost mode
  • h Heat pump stage (dual fuel)
  • ≡ Three bars - back to normal

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox ML180UHEK 100166, Furnace Control Board Low GWP Modes of Operation and LGWP Test Button Functionality (Tables 18-19), printed p.34-35. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.