Lennox · Furnace

P Program unit size (button menu)

Menu / mode display EL296UHVLennox SL280UHVLennox SL280UHNVLennox SL297NV

What the display is showing

Variable speed models only. Used to set the furnace size code after replacing the control.

Applies to: EL296UHV(X) with control 103130-XX or 107045-XX

What to do

  1. Thermostat off, control idle. Hold the button until a solid P shows, release.
  2. P flashes for 90 seconds. Hold the button again and release when the right size code shows (each shows for 3 seconds).
  3. The code then flashes for 10 seconds. Within that time hold the button 5 seconds to store it.
  4. Cycle 24 V power to confirm. If the time runs out or the hold is too short, nothing is changed.

Settings for these units

Recommended filter size by cabinet width · EL296UHV

Cabinet widthSide returnBottom return
17-1/2 in.16 x 25 x 1 in. (1)16 x 25 x 1 in. (1)
21 in.16 x 25 x 1 in. (1)20 x 25 x 1 in. (1)
24-1/2 in.16 x 25 x 1 in. (2)24 x 25 x 1 in. (1)

Number in brackets is the quantity of filters.

Filters are field supplied and installed outside the furnace; inspect monthly.

Recommended filter size by cabinet width · Lennox SL280UHV

Cabinet widthSide returnBottom return
14-1/2 in.16 x 25 x 1 in. (1)14 x 25 x 1 in. (1)
17-1/2 in.16 x 25 x 1 in. (1)16 x 25 x 1 in. (1)
21 in.16 x 25 x 1 in. (1)20 x 25 x 1 in. (1)
24-1/2 in.16 x 25 x 1 in. (2)24 x 25 x 1 in. (1)

Number in brackets is filter quantity; filters are field supplied.

Never run the unit without a filter installed.

Models that show this code

22 models in EL296UHV, Lennox SL280UHV, Lennox SL280UHNV, Lennox SL297NV

EL296UH045XV36BEL296UH070XV36BEL296UH090XV36CEL296UH090XV48CEL296UH090XV60CEL296UH110XV48CEL296UH110XV60CEL296UH135XV60DSL280UH060NV36ASL280UH070V36ASL280UH080NV48BSL280UH080NV60CSL280UH090V36BSL280UH090V48BSL280UH090V60CSL280UH100NV60CSL280UH110V60CSL280UH135V60DSL297UH040NV36BSL297UH060NV36BSL297UH080NV48CSL297UH080NV60C

Other codes on the same units

  • . Idle - no call
  • = Two bars - soft disable
  • A Blower airflow setting
  • E Error recall mode (button menu)
  • F Flame signal mode (button menu)
  • Power-up size code Unit size code shown at power-up (variable speed)
  • U Discharge air temperature
  • c Clear stored errors (inside error recall)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL296UHV(X) Unit Information, Corp 1125-L5 (rev. 03/2022), Tables 4-5 (diagnostic modes and LED codes), printed p.32-33. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.