Lennox · Furnace
30 Low temperature protection (below 40 F)
What the control is telling you
Cooling is blocked until the thermostat reads above 40 F. S30/S40 thermostat alert code 30.
Applies to: Lennox communicating gas furnaces (e.g. SL280UHV/SL280UHNV, EL296UHV) in S30/S40 smart thermostat systems
Likely causes
- Cooling equipment stuck on
- Thermostat sensor reading wrong
Test and repair steps
- Check that cooling equipment is not stuck ON (contactor, compressor).
- Verify the thermostat's temperature sensor reads correctly.
- Use heating mode to warm the space above 40 F.
- Clears automatically once fixed.
Settings for these units
- Recommended filter size by cabinet width · EL296UHV
- Recommended filter size by cabinet width · Lennox SL280UHV
- Filter sizes by cabinet width · Lennox ML180UHE
- Filter sizes (filter rack kits) · Lennox EL195UHNE
- Filter sizes by cabinet width · Lennox SL297NV
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.10. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.