10 flashes Watchguard - pressure switch opened 5 times in one heat demand

High severity Lennox EL195UHNE

What the control is telling you

Pressure switch opened 5 times in one heat call, so the control is in a 1 hour lockout.

Applies to: EL195UHNE furnaces with ignition control 103217-03 or 107163-01 (red LED)

Likely causes

  • Intermittent vent restriction (wind, ice)
  • Partially plugged condensate drain
  • Loose/leaking switch hoses
  • Marginal inducer

Test and repair steps

  1. Check vent terminations for icing or wind effects and that intake/exhaust separation and clearances are correct.
  2. Clean and prime the condensate trap; check the drain line slope (1/4 in. per ft).
  3. Inspect switch hoses and screens.
  4. Measure switch differential during a long run (set point 0.50 in. w.c.).
  5. Reset by cycling power or thermostat after repair.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL195UHNE Unit Information Corp 1801-L1 (rev 04/2024), Table 4 (103217-03) / Table 5 (107163-01) diagnostic codes, p.8-10. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.