5 flashes Watchguard - ignition retries/recycles exceeded
What the control is telling you
The burner failed to light within the maximum retries or recycles. The control locks out and retries after 60 minutes (107163-01: 1 hour lockout).
Applies to: EL195UHNE furnaces with ignition control 103217-03 or 107163-01 (red LED)
Likely causes
- Same causes as 3 flashes: no gas, ignitor, flame sensor, air orifice, vent/drain restriction
Test and repair steps
- Read stored codes (press and release the recall button) to see what led to the lockout.
- Reset by cycling the thermostat off/on or main power.
- Work through the 3-flash checks gas supply, ignitor 39-70 ohms, flame signal, manifold and signal pressure.
- Check intake/exhaust and condensate trap for blockage.
- Watch at least one full ignition sequence after repair.
Settings for these units
- Filter sizes (filter rack kits) · Lennox EL195UHNE
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL195UHNE Unit Information Corp 1801-L1 (rev 04/2024), Table 4 (103217-03) / Table 5 (107163-01) diagnostic codes, p.8-10. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.