Lennox · Furnace
3 flashes Burner failed to light or lost flame
What the control is telling you
The burner did not light, or flame was lost during the heat call.
Applies to: EL195UHNE furnaces with ignition control 103217-03 or 107163-01 (red LED)
Likely causes
- Gas off or low supply pressure
- Ignitor not glowing
- Dirty or poorly placed flame sensor
- Wrong air orifice (hard ignition)
- Poor ground
- Restricted vent/intake or plugged condensate drain
Test and repair steps
- Confirm gas is on at the meter and both manual shut-off valves are open; supply 4.5-10.5 in. w.c. natural gas.
- Watch a cycle 15 s pre-purge, 20 s ignitor warm-up, gas valve opens for a 4 s trial; control retries four more times.
- Check ignitor 39-70 ohms across plug terminals 1 and 5; voltage 120 V +/-10% during warm-up.
- Read flame signal normal 2.6 uA or more, low 2.5 uA or less, drop-out 1.1 uA (Table 7). Note: the troubleshooting flowchart uses 1.5 uA as the low limit. Clean or replace the sensor if low.
- Check manifold pressure 3.2-3.8 in. w.c. (0-4500 ft, natural gas) and signal pressure per Table 19.
- If ignition is rough or delayed, check the air orifice part number against Table 20 and follow the poor ignition/resonance guide.
- Check ground and polarity at the control.
Settings for these units
- Filter sizes (filter rack kits) · Lennox EL195UHNE
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL195UHNE Unit Information Corp 1801-L1 (rev 04/2024), Table 4 (103217-03) / Table 5 (107163-01) diagnostic codes, p.8-10; p.12-13, 40-45. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.