Lennox · Furnace

9 flashes Pressure switch stays open or drops out on a heat call

High severity Lennox EL195UHNE

What the control is telling you

The combustion air pressure switch did not prove within 2-1/2 minutes, or opened while running. The control goes into a 5-minute pressure switch Watchguard.

Applies to: EL195UHNE furnaces with ignition control 103217-03 or 107163-01 (red LED)

Likely causes

  • Blocked or too-long vent/intake
  • Plugged condensate drain or trap backing water into the header box
  • Kinked, cracked or plugged pressure switch hoses or hose screens
  • Weak inducer
  • Failed pressure switch

Test and repair steps

  1. Check intake and exhaust for blockage and that vent lengths are within Table 13.
  2. Check the condensate trap and drain; a blocked drain backs water into the cold end header box and lowers the switch differential.
  3. Pull the rubber hoses off the cold end header box and clean both the hoses and their screens.
  4. Measure the differential across the inducer orifice with a manometer; the switch set point is 0.50 in. w.c. on all sizes.
  5. Confirm the inducer runs at full speed; replace the switch only if differential is above 0.50 in. w.c. and the switch stays open.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL195UHNE Unit Information Corp 1801-L1 (rev 04/2024), Table 4 (103217-03) / Table 5 (107163-01) diagnostic codes, p.8-10; Table 8, p.14; maintenance p.47-48. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.