Lennox · Furnace

11 flashes Pressure switch stuck closed before inducer starts

Medium severity Lennox EL195UHNE

What the control is telling you

The pressure switch is closed before the inducer is energized, so the control will not start the heat cycle.

Applies to: EL195UHNE furnaces with ignition control 103217-03 or 107163-01 (red LED)

Likely causes

  • Pressure switch contacts welded
  • Jumper across the switch
  • Wiring short

Test and repair steps

  1. Warning: Never jumper or bypass the pressure switch.
  2. With the inducer off, check the switch for continuity - it is normally open.
  3. Check wiring at the 12-pin plug (pin 10 pressure switch in) for shorts.
  4. Replace the switch if closed with no differential.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL195UHNE Unit Information Corp 1801-L1 (rev 04/2024), Table 4 (103217-03) / Table 5 (107163-01) diagnostic codes, p.8-10; Table 2, p.8. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.