Lennox · Furnace
7 flashes Primary or secondary limit open
What the control is telling you
A high limit is open, or the control is in Watchguard because a limit stayed open longer than 3 minutes. Gas is off and the blower runs.
Applies to: EL195UHNE furnaces with ignition control 103217-03 or 107163-01 (red LED)
Likely causes
- Dirty filter or restricted return/supply
- Blower on too low a heat speed
- External static too high
- Over-firing (manifold pressure high)
- Failed blower motor
- Failed limit switch
Test and repair steps
- Replace or clean the filter; check that registers and returns are open.
- Measure external static heating speed must not exceed 0.5 in. w.c.
- Measure temperature rise (supply minus return) and set the HEAT speed tap so the rise is within the rating plate range (040: 30-60, 060: 35-65, 080: 40-70, 100: 45-75 F).
- Clock the gas meter (Table 17) and check manifold pressure; correct over-firing.
- Check the blower motor runs on heat speed (24 VAC on the HEAT tap).
- If the limit does not reset within 3 minutes the control waits 60 minutes; cycle power or thermostat to retry after the repair.
Settings for these units
- Filter sizes (filter rack kits) · Lennox EL195UHNE
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL195UHNE Unit Information Corp 1801-L1 (rev 04/2024), Table 4 (103217-03) / Table 5 (107163-01) diagnostic codes, p.8-10; p.11, 40, 46. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.